Analysis of Abnormal Nitrogen Leakage in 500KV Circuit Breaker
DOI:
https://doi.org/10.71222/9a16w343Keywords:
500kV substation, main transformer switch, nitrogen leakage, relay faultAbstract
High-voltage switches are widely used in 500kV substations, where nitrogen leaks are a common occurrence during operation. This paper provides a detailed analysis of the abnormal nitrogen leak incident involving the No.5041 switch of the No.3 main transformer at the 500kV Danxi Substation. By examining the monitoring backend signals, inspecting on-site equipment, and studying the relay circuits, the cause of the anomaly was identified, and effective solutions were proposed. The analysis revealed that the anomaly was caused by a fault in the K15 relay, not a genuine nitrogen leak. The paper summarizes the handling process and the issues exposed, providing a reference for the analysis and handling of similar anomalies.
References
1. R. M. A. Velásquez, J. V. M. Lara and A. Melgar, "Reliability model for switchgear failure analysis applied to ageing," Eng. Fail. Anal., vol. 101, pp. 36–60, 2019, doi: 10.1016/j.engfailanal.2019.03.004.
2. Y. Liu, H. Gao, W. Gao and F. Peng, "Development of a Substation-Area Backup Protective Relay for Smart Substation," IEEE Trans. Smart Grid, vol. 8, no. 6, pp. 2544–2553, Nov. 2017, doi: 10.1109/TSG.2016.2527687.
3. M. S. Naidu, Gas Insulated Substations. IK International Pvt Ltd, 2008. ISBN: 9788190694292.
4. W. Liu, B. Xu, H. Yang et al., "Hydraulic operating mechanisms for high voltage circuit breakers: Progress evolution and future trends," Sci. China Technol. Sci., vol. 54, pp. 116–125, 2011, doi: 10.1007/s11431-010-4154-6.
5. S. Fang, W. Luo, H. Wang and H. Hu, "Operational performance of the valve cooling system in Guangzhou converter station," 11th IET Int. Conf. AC DC Power Transm., Birmingham, 2015, pp. 1–5, doi: 10.1049/cp.2015.0092.
6. X. Yao et al., "Development and Type Test of a Single-Break 126-kV/40-kA–2500-A Vacuum Circuit Breaker," IEEE Trans. Power Del., vol. 31, no. 1, pp. 182–190, Feb. 2016, doi: 10.1109/TPWRD.2015.2456033.
7. J. Li, Z. Jia, S. Wang and S. Liu, "Pressure Characteristics in the Nitrogen-Sealed Power Transformers under Internal Faults," Processes, vol. 12, no. 6, p. 1167, 2024, doi: 10.3390/pr12061167.
8. F. Mohammadi et al., "HVDC Circuit Breakers: A Comprehensive Review," in IEEE Trans. Power Electron., vol. 36, no. 12, pp. 13726-13739, Dec. 2021, doi: 10.1109/TPEL.2021.3073895.
9. B. Xu, R. Ding, J. Zhang, L. Sha and M. Cheng, "Multiphysics-Coupled Modeling: Simulation of the Hydraulic-Operating Mechanism for a SF6 High-Voltage Circuit Breaker," IEEE/ASME Trans. Mechatron., vol. 21, no. 1, pp. 379–393, Feb. 2016, doi: 10.1109/TMECH.2015.2460351.
10. J. Wang, "Research on Spring Defect Detection System of High-Voltage Circuit Breaker in Power System," 2023 3rd Int. Signal Process., Commun. Eng. Manage. Conf. (ISPCEM), Montreal, QC, Canada, 2023, pp. 367–371, doi: 10.1109/ISPCEM60569.2023.00072.
11. X. Wu, S. Zhao, M. Hu and Z. Zhang, "Analysis and Treatment of Frequent Pressure Failures in the AC Filter Field Circuit Breakers of UHV Converter Stations," 2024 IEEE Int. Conf. DC Technol. Syst. (DCTS), Zhuhai, China, 2024, pp. 19–23, doi: 10.1109/DCTS62535.2024.10940039.